NEC Wire Size & Ampacity Calculator
Size conductors per NEC 310.16 with temperature and bundling derates, select the breaker/OCPD (NEC 240), and get a pass/fail code verdict. Voltage drop is reported as advisory.
Sizing a solar array instead? Use the Solar PV Wire Size Calculator (NEC 690.8).
Input Parameters
Maximum continuous current draw
Used only for the voltage-drop estimate
One-way distance (calculator uses round-trip)
Caps the usable ampacity per NEC 110.14(C)
NEC recommends 3% for branch circuits, 5% total
Sizes the breaker and conductor at 125% of load (NEC 210.19 / 210.20)
Loading calculation engine...
Results
Enter parameters and click Calculate
Run calculation to see ampacity table
Wire Sizing Principles
Ampacity
The maximum current a conductor can carry continuously without exceeding its temperature rating. Values come from NEC Table 310.16.
Temperature Correction
When ambient temperature differs from the 30°C base, ampacity must be adjusted per NEC 310.15(B). Higher temperatures reduce the allowable current.
Bundling Adjustment
When more than 3 current-carrying conductors are bundled together, heat dissipation is reduced. NEC 310.15(C) provides adjustment factors.
Voltage Drop
Resistance causes voltage loss along wire length. NEC recommends ≤3% for branch circuits.
Power Loss
References
- NFPA 70: National Electrical Code (NEC), 2020 Edition
- NEC Table 310.16: Conductor Ampacities
- NEC 310.15(B): Ambient Temperature Correction
- NEC 310.15(C): Bundling Adjustment Factors