Solar PV Wire Size Calculator
Size PV source/output conductors per NEC 690.8 from module short-circuit current (Isc), using free-air Table 310.17 ampacity. Sizes the OCPD (690.9) and reports voltage drop as advisory.
Building or premises wiring instead? Use the NEC Wire Size & Ampacity Calculator.
Input Parameters
Module/array Isc from the datasheet
One-way distance (calculator uses round-trip)
Advisory target; ~2% typical for PV
Loading calculation engine...
Results
Enter parameters and click Calculate
PV Conductor Sizing (NEC 690.8)
Maximum circuit current
PV source/output circuit current is 125% of the module or array short-circuit current (NEC 690.8(A)(1)), accounting for irradiance and temperature enhancement.
Conductor ampacity (690.8(B))
The conductor must satisfy both rules: its free-air (Table 310.17) ampacity, before adjustment, must be at least 156.25% of Isc; and after temperature/bundling derating it must still carry the maximum circuit current.
Overcurrent device (690.9)
Where required, the OCPD is rated at 156.25% of Isc, rounded up to a standard rating (NEC 240.6).
Voltage drop (advisory)
Voltage drop is a design consideration for PV (to minimize losses), not an NEC requirement. A ~2% target is typical.
Data & status
Free-air ampacities are from NEC Table 310.17, cross-checked across three references. This tool is Experimental and unverified; verify independently before final design.
References
- NFPA 70: National Electrical Code (NEC)
- NEC 690.8: Circuit sizing and current
- NEC 690.9: Overcurrent protection
- NEC Table 310.17: Free-air conductor ampacities